Reverse action of on-load tap changer in asociation with voltage collapse
Journal Article
·
· IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (USA)
- Kansai Electric Power Co., Inc., Osaka (Japan)
- Tokyo Univ. (Japan)
This paper discusses the reverse action that the secondary voltage of a transformer is pulled down when the tap position of on-load tap changer is raised to increase the secondary voltage. A dynamic model of an induction motor is adopted as a load model simulating this king of reverse action during voltage collapse. The transient mechanisms of the reverse action are analyzed by using P-V curves.
- OSTI ID:
- 6003200
- Journal Information:
- IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (USA), Journal Name: IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (USA) Vol. 6:2; ISSN ITPSE; ISSN 0885-8950