OTEC performance tests of the Union Carbide enhanced-tube condenser

Technical Report ·
DOI:https://doi.org/10.2172/5963405· OSTI ID:5963405
Results of performance tests conducted on a Union Carbide enhanced-tube condenser with wire wrapping on the ammonia side and internal axial fins on the water side are reported. This unit performed satisfactorily and was free of operational difficulties. At design operating conditions (a heat duty of 3.2 million Btu/h, an inlet water temperature of 40/sup 0/F, and a water flow rate of 3200 gpm) the steady-state value of the overall heat transfer coefficient was found to be 818 Btu/h.ft/sup 2/./sup 0/F, and the ammonia-side and water-side heat transfer coefficients were 5180 and 1130 Btu/h.ft/sup 2/./sup 0/F, respectively. The water-side pressure drop was 1.8 psi. Varying the heat duty from 2.4 million to 4.0 million Btu/h had a negligible effect on thermal performance. The value obtained for the ammonia-side heat transfer coefficient at nominal conditions is about two times that predicted by the Nusselt expression for condensation on a smooth tube. The water-side coefficient is within 3% of the value predicted by the Noranda correlation for finned tubes.