Title: Solar-energy-system performance-evaluation update: El Toro Library, El Toro, California, December 1981-August 1982

Technical Report ·
DOI:https://doi.org/10.2172/5959669· OSTI ID:5959669

The El Toro Library is a one-story facility that contains 10,000 square feet of floor area. The solar energy system was designed to provide 97% of the space heating load and 60% of the space cooling load. The solar energy system incorporates 82 panels with a gross area of 1427 square feet of evacuated tubular glass collectors (TC-100) manufactured by General Electric. The storage tank is a 1500-gallon insulated steel tank which is located outside, above ground level. The space heating subsystem uses solar energy from storage and/or thermal energy from the natural-gas-fired boiler. The space cooling subsystem uses an absorption chiller to provide chilled water to the air-handling unit. As compared to the previous year, performance over the nine-month monitoring period was improved, based on overall solar contribution to the load. When compared to design values, the overall performance was poor. Overall solar fraction was an estimated 22% of the 220 million Btu system load. A total of 122 million Btu of solar energy was used by the space conditioning system. Auxiliary fossil fuel consumption was 608 million Btu, or 595,800 cubic feet of natural gas. Auxiliary thermal energy was a measured 68% of the auxiliary fossil fuel consumed. The solar savings ratio, a measure of the solar contribution to the load discounted by solar operating energy, averaged 19% during the analysis period. The previous year, the solar savings ratio was 16%.

Research Organization:
Vitro Labs., Silver Spring, MD (USA)
DOE Contract Number:
AC01-79CS30027
OSTI ID:
5959669
Report Number(s):
SOLAR/2074-83/14; ON: DE83015604
Country of Publication:
United States
Language:
English