Performance of 115 kV fiberglass transmission crossarms in wet and salt fog environments
Journal Article
·
· IEEE Trans. Power Appar. Syst.; (United States)
This paper discusses 60 Hz-dielectric tests performed on 115 kV solid fiberglass transmission crossarm-insulator assemblies to evaluate their performance in wet and salt fog environments. Testing included the following variables: (1) wet and dry conditions, (2) new and used crossarms and insulators, (3) type and number of insulators, and (4) salt fog salinity. Analysis of test results shows that the surface coating of fiberglass insulation is susceptible to degradation in a salt fog environment. Once this coating is eroded and the glass fibers are exposed, carbonized tracking develops. The fiberglass crossarm thus loses its electrical strength.
- Research Organization:
- Shah and Associates, Inc., 4 Professional Drive, Gaithersburg, MD 20879
- OSTI ID:
- 5935829
- Journal Information:
- IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. 102:4; ISSN IEPSA
- Country of Publication:
- United States
- Language:
- English
Similar Records
AC and lightning performance of fiberglass crossarms aged in 115 kV transmission line
The cold-fog test
Tucson-Apache 115-kV reconductor, Pima, Cochise Counties, Arizona: Environmental assessment
Journal Article
·
Fri Oct 01 00:00:00 EDT 1993
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:5313824
The cold-fog test
Journal Article
·
Tue Oct 01 00:00:00 EDT 1996
· IEEE Transactions on Power Delivery
·
OSTI ID:422773
Tucson-Apache 115-kV reconductor, Pima, Cochise Counties, Arizona: Environmental assessment
Technical Report
·
Fri Dec 31 23:00:00 EST 1982
·
OSTI ID:5321973
Related Subjects
200300* -- Electric Power Engineering-- Power Transmission & Distribution-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
42 ENGINEERING
420800 -- Engineering-- Electronic Circuits & Devices-- (-1989)
CHEMICAL REACTIONS
COATINGS
CORROSION
DIELECTRIC PROPERTIES
ELECTRICAL EQUIPMENT
ELECTRICAL INSULATORS
ELECTRICAL PROPERTIES
ELECTRICAL TESTING
EQUIPMENT
FIBERGLASS
FOG
FREQUENCY RANGE
HZ RANGE
MATERIALS TESTING
NONDESTRUCTIVE TESTING
PERFORMANCE
PHYSICAL PROPERTIES
POWER TRANSMISSION LINES
PROTECTIVE COATINGS
SALINITY
TESTING
24 POWER TRANSMISSION AND DISTRIBUTION
42 ENGINEERING
420800 -- Engineering-- Electronic Circuits & Devices-- (-1989)
CHEMICAL REACTIONS
COATINGS
CORROSION
DIELECTRIC PROPERTIES
ELECTRICAL EQUIPMENT
ELECTRICAL INSULATORS
ELECTRICAL PROPERTIES
ELECTRICAL TESTING
EQUIPMENT
FIBERGLASS
FOG
FREQUENCY RANGE
HZ RANGE
MATERIALS TESTING
NONDESTRUCTIVE TESTING
PERFORMANCE
PHYSICAL PROPERTIES
POWER TRANSMISSION LINES
PROTECTIVE COATINGS
SALINITY
TESTING