Performance of 115 kV fiberglass transmission crossarms in wet and salt fog environments

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)
This paper discusses 60 Hz-dielectric tests performed on 115 kV solid fiberglass transmission crossarm-insulator assemblies to evaluate their performance in wet and salt fog environments. Testing included the following variables: (1) wet and dry conditions, (2) new and used crossarms and insulators, (3) type and number of insulators, and (4) salt fog salinity. Analysis of test results shows that the surface coating of fiberglass insulation is susceptible to degradation in a salt fog environment. Once this coating is eroded and the glass fibers are exposed, carbonized tracking develops. The fiberglass crossarm thus loses its electrical strength.
Research Organization:
Shah and Associates, Inc., 4 Professional Drive, Gaithersburg, MD 20879
OSTI ID:
5935829
Journal Information:
IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. 102:4; ISSN IEPSA
Country of Publication:
United States