Negative-sequence overcurrent element application and coordination in distribution protection

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.252618· OSTI ID:5922962
 [1]; ;  [2]
  1. British Columbia Hydro, Vancouver, British Columbia (Canada)
  2. Schweitzer Engineering Lab., Inc., Pullman, WA (United States)
Negative-sequence overcurrent elements do not respond to balanced load and can thus be set to operate faster and more sensitively than phase overcurrent elements for phase-to-phase faults. This paper demonstrates that on a radial distribution system, negative-sequence overcurrent elements need only be coordinated with downstream phase overcurrent devices for phase-to-phase faults. Coordination for other fault types is then achieved with no further analysis required. The effects of negative-sequence load current and open phase conductors on negative-sequence overcurrent elements are also discussed.
OSTI ID:
5922962
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 8:3; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Coordinating overcurrent protection devices
Journal Article · Mon Jul 01 00:00:00 EDT 1996 · IEEE Computer Applications in Power · OSTI ID:287425

Overcurrent protective device coordination by computer
Journal Article · Wed Sep 01 00:00:00 EDT 1982 · IEEE Trans. Ind. Appl.; (United States) · OSTI ID:6366772

Saturating time-delay transformer for overcurrent protection. [Patent application]
Patent · Wed Dec 17 23:00:00 EST 1975 · OSTI ID:7334215