Title: Heat transfer and friction factor correlations for crossflow over staggered finned tube banks

Journal Article · · Heat Transfer Engineering; (USA)
 [1]
  1. Unique Solutions of America, Inc., Bronx, NY (US)

The analysis of visual patterns of flow distribution in finned tube banks with individual fins permits the separation of major factors affecting heat transfer and pressure drop. A flow model and governing dimensionless variables are established on the basis of this analysis and similarity with heat transfer phenomena in channels. Heat transfer and friction factor correlations are recommended for crossflow over staggered tube banks with plain and segmented fins in the range of Reynolds numbers Re{sub h} = 300-10,000. Correlation coefficients are evaluated using original and published experimental data. The correlations correspond with most of the available test data within 10%.

OSTI ID:
5885361
Journal Information:
Heat Transfer Engineering; (USA), Vol. 12:1; ISSN 0145-7632
Country of Publication:
United States
Language:
English