Determination of ac conductor and pipe loss in pipe-type cable systems
Technical Report
·
OSTI ID:5745991
Results are presented of investigations on the determination of ac/dc resistance ratios of high and extra high voltage pipe-type cables with large cross-section segmental conductors. The measurements included 115, 345 and 765 kV cables with copper and aluminum conductors. Conducting and insulating coatings were used on the copper strands. Aluminum strands were covered with their natural oxide coating. Measurements were made in-air and in-pipe in close triangular and cradle configuration. Measurements with cables in-pipe were initially performed at temperatures up to 150/sup 0/C and later only up to 115/sup 0/C. Improved analytical formulations for the calculation of the power losses with the cables in pipe were developed, and the permeability properties of the steel pipes were experimentally determined. Results of the tests performed indicate that similar cables with copper conductors with bare, tin-coated strands exhibit similar ac/dc resistance ratios. Cables with enamel coated copper and aluminum strands have lower ac/dc resistance ratios than the above cables. Tests performed at room temperature, after exposing the conductor to elevated temperatures, indicate that in some cases the room temperature ac/dc resistance ratios are affected by the maximum temperature to which the conductor was exposed. Comparison of measured values with calculated values (using the Neher-McGrath method) confirms that this method can also be used for aluminum conductors at room temperature and for copper and aluminum conductors at operating temperature. The accuracy of the Neher-McGrath method has been improved by the use of a new transverse conductance facter k/sub pc/ and a new in-pipe factor. The method developed provided only a limited agreement between calculated and measured values. The attainable accuracy is circumscribed by the nature of the boundary conditions, and by the limitation on the detail which can be modelled.
- Research Organization:
- General Cable Corp., Union, NJ (USA)
- OSTI ID:
- 5745991
- Report Number(s):
- EPRI-EL-1125
- Country of Publication:
- United States
- Language:
- English
Similar Records
Determination of ac conductor and pipe loss in pipe-type cable systems. Final report
Calculating ac/dc resistance ratios for high-pressure oil-filled cable Designs. Volume 1. Designer's guide. Final report
Determination of the effect of harmonics on pipe-type power cable AC/DC resistance ratio
Technical Report
·
Sun Jan 31 23:00:00 EST 1982
·
OSTI ID:5663309
Calculating ac/dc resistance ratios for high-pressure oil-filled cable Designs. Volume 1. Designer's guide. Final report
Technical Report
·
Sun Mar 31 23:00:00 EST 1985
·
OSTI ID:5802162
Determination of the effect of harmonics on pipe-type power cable AC/DC resistance ratio
Journal Article
·
Sun Feb 28 23:00:00 EST 1993
· IEEE Transactions on Magnetics (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6411065
Related Subjects
200301* -- Power Transmission & Distribution-- AC Systems
EHV & UHV-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
AC LOSSES
AC SYSTEMS
CABLES
COMPUTER CALCULATIONS
CONDUCTOR DEVICES
DATA
DATA FORMS
EHV AC SYSTEMS
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
EQUIPMENT
EXPERIMENTAL DATA
GRAPHS
HVAC SYSTEMS
INFORMATION
MEASURING METHODS
NUMERICAL DATA
PIPES
POWER SYSTEMS
POWER TRANSMISSION
TABLES
TEMPERATURE DEPENDENCE
THEORETICAL DATA
UNDERGROUND POWER TRANSMISSION
EHV & UHV-- (-1989)
24 POWER TRANSMISSION AND DISTRIBUTION
AC LOSSES
AC SYSTEMS
CABLES
COMPUTER CALCULATIONS
CONDUCTOR DEVICES
DATA
DATA FORMS
EHV AC SYSTEMS
ELECTRIC CABLES
ELECTRICAL EQUIPMENT
EQUIPMENT
EXPERIMENTAL DATA
GRAPHS
HVAC SYSTEMS
INFORMATION
MEASURING METHODS
NUMERICAL DATA
PIPES
POWER SYSTEMS
POWER TRANSMISSION
TABLES
TEMPERATURE DEPENDENCE
THEORETICAL DATA
UNDERGROUND POWER TRANSMISSION