Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Microprocessor based three step quadrilateral distance relay for the protection of EHV/UHV transmission lines

Journal Article · · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
DOI:https://doi.org/10.1109/61.108894· OSTI ID:5709974
;  [1]
  1. Dept. of Electrical and Electronics Engineering, PSG College of Technology, Coimbatore-6411 004 (IN)
This paper deals with the development of a 3-zone quadrilateral distance relay for the protection of EHV/UHV transmission lines. The proposed scheme is based on the Fourier Transform method of extracting the fundamental components of voltage and current signals from non-sinusoidal post fault signals. The determination of the quadrilateral characteristic is completed through software. The relay is successfully tested for a number of different three step quadrilateral characteristics and the results are obtained. Any quadrilateral characteristic can be obtained. Recommendations are made to use 16-bit processors to reduce the operating time and for better accuracy.
OSTI ID:
5709974
Journal Information:
IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States), Journal Name: IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) Vol. 7:1; ISSN 0885-8977; ISSN ITPDE
Country of Publication:
United States
Language: