Simulator study of multiterminal HVDC transmission system without fast communication

Journal Article · · IEEE Trans. Power Del.; (United States)

AC/DC simulator studies for a 4-terminal HVDC system have been carried out to demonstrate the operating performance of the multi-terminal HVDC control scheme, ''the 2-ACR method'', which does not require fast communication systems. A microcomputer is used for converter control. Satisfactory operations have been confirmed through various types of simulations. Examples of an effective and economical DC circuit breaker application, for an AC system fault at the inverter and a DC line fault, are described.

Research Organization:
Tokyo Electric Power Co., Tokyo
OSTI ID:
5708734
Journal Information:
IEEE Trans. Power Del.; (United States), Journal Name: IEEE Trans. Power Del.; (United States) Vol. PWRD-1:3; ISSN ITPDE
Country of Publication:
United States
Language:
English