Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Environmental assessment of NH3 injection for an industrial package boiler. Volume 2. Data supplement. Final report, January 1983-January 1984

Technical Report ·
OSTI ID:5694677
The report discusses emission results from comprehensive flue-gas sampling of a gas- and oil-fired industrial boiler equipped with Exxon's Thermal DeNOx Ammonia Injection Process for NOx reduction. Comprehensive emission measurements included continuous monitoring of flue gas emissions; source assessment sampling system (SASS) tests; EPA Method 5/17 for solid and condensible particulate emissions and ammonia emissions; controlled condensation system for SO2 and SO3; and N2O emission sampling. Ammonia injection at a NH3/NO molar ratio of 2.52 gave a NOx reduction of 41% from an uncontrolled level of 234 ppm to a controlled level of 137 ppm. NH3 emissions increased from 11 ppm for the baseline to an average of 430 ppm for ammonia injection. Nitrous oxide, N2O, was reduced 68% from a 50 ppm baseline level to a 17 ppm controlled level. Total particulate emissions increased by an order of magnitude from a baseline of 17.7 ng/J to a controlled level of 182 ng/J.
Research Organization:
Acurex Corp., Mountain View, CA (USA). Energy and Environmental Div.
OSTI ID:
5694677
Report Number(s):
PB-86-182409/XAB; ACUREX/TR-83-139/EE-VOL-2
Country of Publication:
United States
Language:
English