Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Control room envelope unfiltered air inleakage test protocols

Conference ·
OSTI ID:567198
 [1];  [2]
  1. Lagus Applied Technology, San Diego, CA (United States)
  2. Lagus Applied Technology, Olney, MD (United States)
In 1983, the Advisory Committee on Reactor Safeguards (ACRS) recommended that the US NRC develop a control room HVAC performance testing protocol. To date no such protocol has been forthcoming. Beginning in mid-1994, an effort was funded by NRC under a Small Business Innovation Research (SBIR) grant to develop several simplified test protocols based on the principles of tracer gas testing in order to measure the total unfiltered inleakage entering a CRE during emergency mode operation of the control room ventilation system. These would allow accurate assessment of unfiltered air inleakage as required in SRP 6.4. The continuing lack of a standard protocol is unfortunate since one of the significant parameters required to calculate operator dose is the amount of unfiltered air inleakage into the control room. Often it is assumed that, if the Control Room Envelope (CRE) is maintained at +1/8 in. w.g. differential pressure relative to the surroundings, no significant unfiltered inleakage can occur it is further assumed that inleakage due to door openings is the only source of unfiltered air. 23 refs., 13 figs., 2 tabs.
Research Organization:
Harvard Univ., Boston, MA (United States). Harvard Air Cleaning Lab.; USDOE Assistant Secretary for Environment, Safety, and Health, Washington, DC (United States). Office of Environmental Guidance; Nuclear Regulatory Commission, Washington, DC (United States). Office of Nuclear Regulatory Research; International Society of Nuclear Air Treatment Technologies, Inc., Batavia, OH (United States)
OSTI ID:
567198
Report Number(s):
NUREG/CP--0153; CONF-960715--; ON: TI97008959; CNN: Grant NRC-04-94-070
Country of Publication:
United States
Language:
English

Similar Records

Multinodal control room envelope model used for habitability analysis
Journal Article · Sat Dec 30 23:00:00 EST 1995 · Transactions of the American Nuclear Society · OSTI ID:411749

MULTI - TRACER CONTROL ROOM AIR INLEAKAGE PROTOCOL AND SIMULATED PRIMARY AND EXTENDED MULTI - ZONE RESULTS.
Technical Report · Mon Dec 31 23:00:00 EST 2001 · OSTI ID:794089

New technologies for a postaccident control room habitability assessment
Conference · Thu Dec 31 23:00:00 EST 1992 · Transactions of the American Nuclear Society; (United States) · OSTI ID:6912367