Title: Underestimation of oxygen deficiency hazard through use of linearized temperature profiles

Technical Report ·
DOI:https://doi.org/10.2172/5654324· OSTI ID:5654324

The failure mode analysis for any cryogenic system includes the effects of a large liquid spill due to vessel rupture or overfilling. The Oxygen Deficiency Hazard (ODH) analysis for this event is a strong function of the estimated heat flux entering the spilled liquid. A common method for estimating the heat flux is to treat the surface on which the liquid spills as a semi-infinite solid. This note addresses the effect of linearizing the temperature profile in this form of analysis, and shows it to cause the calculated flux to be underestimated by more than a factor of two. 3 refs., 2 figs.