Santa Clara, California, Community Center commercial solar demonstration. Progress report: six months data acquisition and analysis of cooling performance
Technical Report
·
OSTI ID:5599271
The Santa Clara Community Center is a 27,000 sq. ft one-story building set in a Mediterranean climate. The peak summer cooling load for the building is estimated to be 5.9 x 10/sup 6/ Btu/day and is roughly twice the estimated peak winter heating load. The solar-driven hydronic system includes 7085 sq. ft of double-glazed flat plate collectors with a selective coating, two 25-ton ARKLA absorption chillers, a 50,000 gallon stratified cold storage tank and a 10,000 gallon hot storage tank. A gas-fired boiler is used for backup. A minicomputer controlled data acquisition system has been providing operational data including detailed energy balances since April 1977. Detailed results for the period of April 1977 to September 1978 are presented. The solar heating and cooling system has performed successfully and dependably during its first two years of operation. Solar collector and absorption chiller performance is lower than expected. System performance during the summer seasons is about the same as predicted giving a solar fraction of load of 0.65. Performance during the winter season is much lower than predicted with a solar fraction of load of 0.40 compared to a predicted value of 0.80. Fossil fuel energy consumption of the system is greater than the estimated consumption of the original non-solar design during some months of the summer season. On an annual basis there is a net savings of fossil energy of about 8 percent.
- Research Organization:
- Santa Clara Univ., CA (USA). Dept. of Mechanical Engineering
- OSTI ID:
- 5599271
- Report Number(s):
- SAN-1083-79/1
- Country of Publication:
- United States
- Language:
- English
Similar Records
Santa Clara, California, community center commercial solar demonstration progress report. Six months data acquisition and analysis of cooling performance
Santa Clara, California, Community Center commercial solar demonstration design and construction report
Performance evaluation of the New Mexico State University Solar House. Technical completion report, January 1, 1978-June 30, 1979
Technical Report
·
Tue Feb 28 23:00:00 EST 1978
·
OSTI ID:6563920
Santa Clara, California, Community Center commercial solar demonstration design and construction report
Technical Report
·
Thu Sep 01 00:00:00 EDT 1977
·
OSTI ID:6742933
Performance evaluation of the New Mexico State University Solar House. Technical completion report, January 1, 1978-June 30, 1979
Book
·
Wed Dec 31 23:00:00 EST 1980
·
OSTI ID:6666120
Related Subjects
14 SOLAR ENERGY
140901* -- Solar Thermal Utilization-- Space Heating & Cooling
BUILDINGS
CALIFORNIA
COMMERCIAL BUILDINGS
COOLING LOAD
DATA ACQUISITION SYSTEMS
DESIGN
ECONOMIC ANALYSIS
ECONOMICS
EQUIPMENT
FLAT PLATE COLLECTORS
HEATING LOAD
HEATING SYSTEMS
INCLINATION
NORTH AMERICA
OPERATION
PERFORMANCE
PUBLIC BUILDINGS
SOLAR COLLECTORS
SOLAR COOLING SYSTEMS
SOLAR EQUIPMENT
SOLAR HEATING SYSTEMS
USA
WESTERN REGION
140901* -- Solar Thermal Utilization-- Space Heating & Cooling
BUILDINGS
CALIFORNIA
COMMERCIAL BUILDINGS
COOLING LOAD
DATA ACQUISITION SYSTEMS
DESIGN
ECONOMIC ANALYSIS
ECONOMICS
EQUIPMENT
FLAT PLATE COLLECTORS
HEATING LOAD
HEATING SYSTEMS
INCLINATION
NORTH AMERICA
OPERATION
PERFORMANCE
PUBLIC BUILDINGS
SOLAR COLLECTORS
SOLAR COOLING SYSTEMS
SOLAR EQUIPMENT
SOLAR HEATING SYSTEMS
USA
WESTERN REGION