Evaluating high-temperature intumescent insulation materials under fire and blast conditions

Conference ·
OSTI ID:543470
 [1]
  1. Hughes Associates, Inc., Baltimore, MD (United States)

This paper describes recent testing conducted to evaluate the performance of high-temperature intumescent materials under adverse fire and blast conditions. Results from fire performance evaluations currently protecting offshore oil platforms are presented. Extensive fire and blast qualification testing of epoxy-based intumescent materials has been conducted utilizing specially designed blast chambers, jet fire facilities, and laboratory furnaces. Blast chambers are capable of loading up to a 3 x 3-m insulated bulkhead assembly to a 2 bar over pressure and having a duration of approximately 250 millisecond generated by a controlled flammable vapor cloud explosion. The jet fire test exposes an insulated test specimen to a fire environment characterized by temperatures of approximately 1100 C, sonic gas velocities, and peak heat flux levels in excess of 300 kW/m{sup 2}.

OSTI ID:
543470
Report Number(s):
CONF-970582--
Country of Publication:
United States
Language:
English

Similar Records

Thermal performance of glass fiber reinforced intumescent fire retardant coating for structural applications
Journal Article · Wed Jul 22 00:00:00 EDT 2015 · AIP Conference Proceedings · OSTI ID:22488603

Fire resistance properties of ceramic wool fiber reinforced intumescent coatings
Journal Article · Wed Jul 22 00:00:00 EDT 2015 · AIP Conference Proceedings · OSTI ID:22488632

Fire performance, microstructure and thermal degradation of an epoxy based nano intumescent fire retardant coating for structural applications
Journal Article · Wed Jul 22 00:00:00 EDT 2015 · AIP Conference Proceedings · OSTI ID:22488600