Life of fluorescent lamps operated at high frequencies with solid-state ballasts

Conference ·
OSTI ID:5387292
Standard 40-watt, F-40, rapid-start, fluorescent lamps were operated with solid-state ballasts following the standard life-testing cycle of 3 hours on and 20 minutes off for more than 20,000 hours at high frequency. Lamp operating characteristics (starting voltage, filament voltage, arc current, and current-crest factor) were studied as factors affecting lamp life. Measurements show that fluorescent lamps can attain rated life at high frequency using solid-state ballasts. When lamps are operated in the dimmed mode, full filament power is required to sustain lamplife. The rate of lamp lumen depreciation is dependent on the lamp loading and not the operating frequency.
Research Organization:
Lawrence Berkeley Lab., CA (USA)
DOE Contract Number:
AC03-76SF00098
OSTI ID:
5387292
Report Number(s):
LBL-19778; CONF-851071-4; EEB-L-85-06; ON: DE85017647