Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Fault and partial discharge location systems for gas-insulated transmission lines. Final report

Technical Report ·
OSTI ID:5349544
Partial discharge and faults in gas-insulated transmission line (GITL) can be difficult to locate. This report describes the development, testing, and application of systems for fault and partial discharge location in GITL. Both systems are based on timing of electromagnetic transients generated by a fault/partial discharge source. Both systems employ microcomputers to facilitate automated data acquisition and analysis. The major problems solved in developing the fault location system were coupling of high frequency signals from and between phases and isolation of high voltage short risetime signals from high speed digital logic. The problems addressed in the partial discharge location project include handling a large number of pulses which may include noise, the large dynamic range of partial discharge induced transients (> 80 dB), and achieving an accurate correlation resolution of 2 ns.
Research Organization:
Ontario Hydro Research Lab., Toronto (Canada)
OSTI ID:
5349544
Report Number(s):
EPRI-EL-3313; ON: DE84920143
Country of Publication:
United States
Language:
English

Similar Records

Electromagnetic techniques for fault and partial discharge location in gas-insulated cables and substations
Journal Article · Thu Jul 01 00:00:00 EDT 1982 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6456222

Location and characterization of partial discharge sites in shielded power cables
Journal Article · Sat Mar 31 23:00:00 EST 1990 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) · OSTI ID:7080681

Locating Partial Discharges in Power Transformers with Convolutional Iterative Filtering