Emergency control of synchronous and nonsynchronous tie lines

Journal Article · · Power Eng. (N.Y., Engl. Transl.); (United States)
OSTI ID:5342673
It is shown that for power systems using ''weak'' synchronous tie lines (ac lines), by employing backup separation with a mutual angle exceeding the critical value and allocating a portion of the generators to the receiving power system, it is possible to achieve synchronous-tie emergency-control capabilities close to those provided by emergency control of a nonsynchronous tie (a line and dc link as well as a line with electromechanical converters).
OSTI ID:
5342673
Journal Information:
Power Eng. (N.Y., Engl. Transl.); (United States), Journal Name: Power Eng. (N.Y., Engl. Transl.); (United States) Vol. 18:6; ISSN POEND
Country of Publication:
United States
Language:
English

Similar Records

Evaluation of harmonic levels on an hvdc transmission line
Journal Article · Sat Dec 31 23:00:00 EST 1966 · Proc. Am. Power Conf.; (United States) · OSTI ID:5921450

Study of fast synchronous-reclosing method for parallel AC line fault in AC/DC power transmission system
Journal Article · Fri Jun 01 00:00:00 EDT 1984 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6265648

Gemini Synchronous Inverter
Journal Article · Sun Feb 29 23:00:00 EST 1976 · Sol. Age; (United States) · OSTI ID:7336338