AC breakdown strengths of N{sub 2}, SF{sub 6} and a mixture of N{sub 2}+SF{sub 6} containing 1% of SF{sub 6} were experimentally studied. For this purpose, 50 Hz AC breakdown voltages in both uniform and non-uniform fields up to a pressure of 400 kPa from 50 kPa were measured. Test results show that the addition of 1% of SF{sub 6} to nitrogen increases the breakdown voltage up to 250 kPa in a non-uniform field. The relative breakdown strength of the mixture with respect to components was also calculated in 50 Hz AC voltage. The analysis of Paschen curves reveals an improvement of 40% in the breakdown strength of mixture in uniform field but in non-uniform fields, the maximum AC breakdown voltage of the mixture is 24% lower than that of pure SF{sub 6}.
- OSTI ID:
- 529630
- Report Number(s):
- CONF-960614--; ISBN 0-7803-3531-7
- Country of Publication:
- United States
- Language:
- English
Similar Records
Dielectric strength of gas mixtures comprising SF/sub 6/, CO, c-C/sub 4/-F/sub 8/ and SF/sub 6/, N/sub 2/, c-C/sub 4/F/sub 8/
Effect of ionization processes on the corona stabilization breakdown in SF/sub 6/ and SF/sub 6/ mixtures
The effect of initiatory electrons on breakdown characteristics in highly nonuniform gap
Journal Article
·
Sun May 01 00:00:00 EDT 1983
· IEEE Trans. Power Appar. Syst.; (United States)
·
OSTI ID:5945346
Effect of ionization processes on the corona stabilization breakdown in SF/sub 6/ and SF/sub 6/ mixtures
Conference
·
Fri Dec 31 23:00:00 EST 1982
·
OSTI ID:5717843
The effect of initiatory electrons on breakdown characteristics in highly nonuniform gap
Conference
·
Mon Dec 30 23:00:00 EST 1996
·
OSTI ID:529636