Surge-suppressing resistors applied to 345- and 500-kV disconnect switches

Conference · · Proc. Am. Power Conf.; (United States)
OSTI ID:5274121
 [1]; ;
  1. Allis-Chalmers Corp., Portland, OR

The use of a simple 345- or 500-kV disconnect switch which can be adapted for safety switching bus sections and/or unloaded transformers is described. The switch-mounted resistors can be quite effective in suppressing overvoltage transients on both energization and deenergization. They also significantly reduce unloaded transformer inrush crrents on energization. By switching the load with low side breakers, the initial cost and maintenance can be reduced. This is particularly true if the high voltage breaker or interrupter has preinsertion resistors in both the opening and closing cycle.

OSTI ID:
5274121
Journal Information:
Proc. Am. Power Conf.; (United States), Journal Name: Proc. Am. Power Conf.; (United States) Vol. 38; ISSN PAPWA
Country of Publication:
United States
Language:
English