This report describes the results of tests conducted on three different designs of full-size electrical penetration assemblies (EPAs) that are used in the containment buildings of nuclear power plants. The objective of the tests was to evaluate the behavior of the EPAs under simulated severe accident conditions using steam at elevated temperature and pressure. Leakage, temperature, and cable insulation resistance were monitored throughout the tests. Nuclear-qualified EPAs were produced from D. G. O'Brien, Westinghouse, and Conax. Severe-accident-sequence analysis was used to generate the severe accident conditions (SAC) for a large dry pressurized-water reactor (PWR), a boiling-water reactor (BWR) Mark I drywell, and a BWR Mark III wetwell. Based on a survey conducted by Sandia, each EPA was matched with the severe accident conditions for a specific reactor type. This included the type of containment that a particular EPA design was used in most frequently. Thus, the D. G. O'Brien EPA was chosen for the PWR SAC test, the Westinghouse was chosen for the Mark III test, and the Conax was chosen for the Mark I test. The EPAs were radiation and thermal aged to simulate the effects of a 40-year service life and loss-of-coolant accident (LOCA) before the SAC tests were conducted. The design, test preparations, conduct of the severe accident test, experimental results, posttest observations, and conclusions about the integrity and electrical performance of each EPA tested in this program are described in this report. In general, the leak integrity of the EPAs tested in this program was not compromised by severe accident loads. However, there was significant degradation in the insulation resistance of the cables, which could affect the electrical performance of equipment and devices inside containment at some point during the progression of a severe accident. 10 refs., 165 figs., 16 tabs.
Research Organization:
Nuclear Regulatory Commission, Washington, DC (USA). Div. of Engineering Standards; Sandia National Labs., Albuquerque, NM (USA)
Sponsoring Organization:
NRC
DOE Contract Number:
AC04-76DP00789
OSTI ID:
5265225
Report Number(s):
NUREG/CR-5334; SAND--89-0327; ON: TI90003511
Country of Publication:
United States
Language:
English

Similar Records

Electrical penetration assemblies severe accident testing
Conference · Tue Dec 31 23:00:00 EST 1985 · OSTI ID:7242894

Leak behavior through EPAs under severe accident conditions
Conference · Tue Dec 31 23:00:00 EST 1985 · OSTI ID:5692005

Investigation of Containment Flooding Strategy for Mark-III Nuclear Power Plant with MAAP4