Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Aerosol penetration through a seismically loaded shear wall

Conference ·
OSTI ID:5251128
An experimental study was performed to measure the aerosol penetration through a reinforced concrete shear wall after simulated seismic damage. Static load-cycle testing, to stress levels sufficient to induce visible shear cracking, was used to simulate the earthquake loading. Air permeability tests were performed both before and after the simulated seismic loading damaged the structure. Aerosol penetration measurements were conducted on the cracked shear wall structure using 0.10 {mu}m monodisperse particles. The measured aerosol number penetration through the cracked shear wall was 0.5%. 7 refs.
Research Organization:
Los Alamos National Lab., NM (United States)
Sponsoring Organization:
DOE; USDOE, Washington, DC (United States)
DOE Contract Number:
W-7405-ENG-36
OSTI ID:
5251128
Report Number(s):
LA-UR-92-1234; CONF-920823--1; ON: DE92013551
Country of Publication:
United States
Language:
English