Title: Calmac Ice Storage Test report

Abstract

The Ice Storage Test Facility (ISTF) is designed to test commercial ice storage systems. Calmac provided a storage tank equipped with coils designed for use with a secondary fluid system. The Calmac ice storage system was tested over a wide range of operating conditions. Measured system performance during charging was similar to that reported by the manufacturer. Both the measured average and minimum brine temperatures were in close agreement with Calmac's literature values, and the ability to fully charge the tank was relatively unaffected by charging rate and brine flow rate. During discharge cycles, the storage tank outlet temperature was strongly affected by the discharge rate. The discharge capacity was dependent upon both the selected discharge rate and maximum allowable tank outlet temperature. Based on these tests, storage tank selection must depend most strongly on the discharge conditions required to serve the load. This report describes Calmac system performance fully under both charging and discharging conditions. Companion reports describe ISTF test procedures and ice-making efficiency test results that are common to many of the units tested. 11 refs., 31 figs., 9 tabs.

Authors:
Publication Date:
Research Org.:
Oak Ridge National Lab., TN (United States)
Sponsoring Org.:
EPRI; Electric Power Research Inst., Palo Alto, CA (United States)
OSTI Identifier:
5210651
Report Number(s):
ORNL/TM-11582
ON: DE92000416
DOE Contract Number:
AC05-84OR21400
Resource Type:
Technical Report
Country of Publication:
United States
Language:
English
Subject:
25 ENERGY STORAGE; 32 ENERGY CONSERVATION, CONSUMPTION, AND UTILIZATION; COLD STORAGE; OFF-PEAK ENERGY STORAGE; REFRIGERATING MACHINERY; PERFORMANCE TESTING; BRINES; FLOW RATE; GLYCOLS; ICE; REFRIGERANTS; TANKS; WATER; ALCOHOLS; CONTAINERS; ENERGY STORAGE; FLUIDS; HYDROGEN COMPOUNDS; HYDROXY COMPOUNDS; MACHINERY; ORGANIC COMPOUNDS; OXYGEN COMPOUNDS; STORAGE; TESTING; WORKING FLUIDS; 250600* - Energy Storage- Thermal; 320106 - Energy Conservation, Consumption, & Utilization- Building Equipment- (1987-)

Citation Formats

Stovall, T.K. Calmac Ice Storage Test report. United States: N. p., 1991. Web. doi:10.2172/5210651.
Stovall, T.K. Calmac Ice Storage Test report. United States. doi:10.2172/5210651.
Stovall, T.K. Thu . "Calmac Ice Storage Test report". United States. doi:10.2172/5210651. https://www.osti.gov/servlets/purl/5210651.
@article{osti_5210651,
title = {Calmac Ice Storage Test report},
author = {Stovall, T.K.},
abstractNote = {The Ice Storage Test Facility (ISTF) is designed to test commercial ice storage systems. Calmac provided a storage tank equipped with coils designed for use with a secondary fluid system. The Calmac ice storage system was tested over a wide range of operating conditions. Measured system performance during charging was similar to that reported by the manufacturer. Both the measured average and minimum brine temperatures were in close agreement with Calmac's literature values, and the ability to fully charge the tank was relatively unaffected by charging rate and brine flow rate. During discharge cycles, the storage tank outlet temperature was strongly affected by the discharge rate. The discharge capacity was dependent upon both the selected discharge rate and maximum allowable tank outlet temperature. Based on these tests, storage tank selection must depend most strongly on the discharge conditions required to serve the load. This report describes Calmac system performance fully under both charging and discharging conditions. Companion reports describe ISTF test procedures and ice-making efficiency test results that are common to many of the units tested. 11 refs., 31 figs., 9 tabs.},
doi = {10.2172/5210651},
journal = {},
number = ,
volume = ,
place = {United States},
year = {Thu Aug 01 00:00:00 EDT 1991},
month = {Thu Aug 01 00:00:00 EDT 1991}
}

Technical Report:

Save / Share: