Speed loop cancellation governor for hydrogenerators - Part II: Application

Journal Article · · IEEE Trans. Power Electronics; (United States)
OSTI ID:5205415
The essential dynamics for a hydrogenerator supplying a large grid may be represented by two control loops: the first for power and the second for speed. Part One of this work develops a governor design intended to neutralize the speed loop's destabilizing effects while tuning for improved load tracking. This paper considers the practical implementation of such a controller by computer. An approximate system is used to develop analytical expressions for the control parameters. These parameters are functions of load level throughout the operating range and may be computed in real time. The effectiveness of the approximate-system-derived control is verified by simulation. Computed transients are indistinguishable from transients for the optimally tuned control.
Research Organization:
Dept. of General Engineering, Univ. of Illinois (US)
OSTI ID:
5205415
Journal Information:
IEEE Trans. Power Electronics; (United States), Journal Name: IEEE Trans. Power Electronics; (United States) Vol. 3:1; ISSN ITCNE
Country of Publication:
United States
Language:
English

Similar Records

Speed loop cancellation governor for hydrogenerators - Part I: Development
Journal Article · Mon Feb 29 23:00:00 EST 1988 · IEEE Trans. Power Electronics; (United States) · OSTI ID:5166391

A state-space pressure and speed sensing governor for hydrogenerators
Journal Article · Sun Sep 01 00:00:00 EDT 1991 · IEEE Transactions on Energy Conversion (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5514651

A graphical approach to hydrogenerator governor tuning