Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Development and interrupting tests on 250KV 8KA HVDC circuit breaker

Journal Article · · IEEE Trans. Power Appar. Syst.; (United States)

This paper describes the circuit and component selections, development and equivalent circuit test results on an HVDC circuit breaker for an HVDC transmission line. A puffer type SF/sub 6/ gas interrupter for AC circuit breakers is utilized for interrupting DC current with injection of high-frequency inverse current from a commutating capacitor precharged to HVDC line voltage. Also, the effectiveness of application of the HVDC breaker to an HVDC system with two parallel transmission lines is demonstrated through the EMTP simulation.

Research Organization:
Hitachi, Ltd., Hitachi City
OSTI ID:
5125352
Journal Information:
IEEE Trans. Power Appar. Syst.; (United States), Journal Name: IEEE Trans. Power Appar. Syst.; (United States) Vol. PAS-104:9; ISSN IEPSA
Country of Publication:
United States
Language:
English