skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Health-hazard evaluation report HETA 87-063-1808, Presbyterian Day Surgery Center, Albuquerque, New Mexico

Technical Report ·
OSTI ID:5015182

In response to a request from employees to evaluate exposures to waste anesthetic gases and vapors at the Presbyterian Day Surgery Unit, located in Albuquerque, New Mexico, personal and area air-sampling and leak-detection testing was carried out for nitrous oxide (N/sub 2/O) and halogenated anesthetic agents in the six operating rooms at the facility. Nitrous oxide concentrations ranged from not detectable to 95 parts per million (ppm) with a mean of 20ppm. Five of the samples exceeded the NIOSH limit of 25ppm for N/sub 2/O during anesthetic administration. Ethrane levels in 14 personal and area air samples ranged from less than the limit of detection to 3.63ppm with a mean of 0.31ppm. Isoflurane and halothane were below the limits of detection. The ventilation system in use changed the air in excess of 20 times per hour. However, during a portion of surgical procedures the system was not operating, resulting in a higher than normal exposure level in three of the operating rooms.

Research Organization:
National Inst. for Occupational Safety and Health, Cincinnati, OH (USA)
OSTI ID:
5015182
Report Number(s):
PB-88-153259/XAB; HETA-87-063-1808
Country of Publication:
United States
Language:
English