Deliberate ignition of hydrogen-air-steam mixtures in condensing steam environments
Large scale experiments were performed to determine the effectiveness of thermal glow plug igniters to burn hydrogen in a condensing steam environment due to the presence of water sprays. The experiments were designed to determine if a detonation or accelerated flame could occur in a hydrogen-air-steam mixture which was initially nonflammable due to steam dilution but was rendered flammable by rapid steam condensation due to water sprays. Eleven Hydrogen Igniter Tests were conducted in the test vessel. The vessel was instrumented with pressure transducers, thermocouple rakes, gas grab sample bottles, hydrogen microsensors, and cameras. The vessel contained two prototypic engineered systems: (1) a deliberate hydrogen ignition system and (2) a water spray system. Experiments were conducted under conditions scaled to be nearly prototypic of those expected in Advanced Light Water Reactors (such as the Combustion Engineering (CE) System 80+), with prototypic spray drop diameter, spray mass flux, steam condensation rates, hydrogen injection flow rates, and using the actual proposed plant igniters. The lack of any significant pressure increase during the majority of the burn and condensation events signified that localized, benign hydrogen deflagration(s) occurred with no significant pressure load on the containment vessel. Igniter location did not appear to be a factor in the open geometry. Initially stratified tests with a stoichiometric mixture in the top showed that the water spray effectively mixes the initially stratified atmosphere prior to the deflagration event. All tests demonstrated that thermal glow plugs ignite hydrogen-air-steam mixtures under conditions with water sprays near the flammability limits previously determined for hydrogen-air-steam mixtures under quiescent conditions. This report describes these experiments, gives experimental results, and provides interpretation of the results. 12 refs., 127 figs., 16 tabs.
- Research Organization:
- Nuclear Regulatory Commission, Washington, DC (United States). Div. of Systems Technology; Sandia National Labs., Albuquerque, NM (United States)
- Sponsoring Organization:
- Nuclear Regulatory Commission, Washington, DC (United States)
- DOE Contract Number:
- AC04-94AL85000
- OSTI ID:
- 489641
- Report Number(s):
- NUREG/CR--6530; SAND--94-1676; ON: TI97006820
- Country of Publication:
- United States
- Language:
- English
Similar Records
Deliberate ignition of hydrogen-air-steam mixtures under conditions of rapidly condensing steam
Deliberate ignition of hydrogen-air-steam mixtures under conditions of rapidly condensing steam
Preliminary results of thermal igniter experiments in H/sub 2/-air-steam environments. [PWR; BWR]
Conference
·
Sat Dec 31 23:00:00 EST 1994
·
OSTI ID:10118638
Deliberate ignition of hydrogen-air-steam mixtures under conditions of rapidly condensing steam
Conference
·
Sat Oct 01 00:00:00 EDT 1994
·
OSTI ID:54565
Preliminary results of thermal igniter experiments in H/sub 2/-air-steam environments. [PWR; BWR]
Conference
·
Wed Dec 31 23:00:00 EST 1980
·
OSTI ID:6618004