The average leakage rate was less than 0.3 pound per year per linear inch of gasket when mockups of typical joints proposed for the reactor vessel and the isolated coolant loops of the HWCTR were subjected to temperature and pressure cycling. The joints, which were exposed to deionized light water, were cycled about 100 times from 70 deg C and atmospheric pressure to 250 deg C and pressures of 1500 psig for the vessel joints and 750 psig for the joints designed for the isolated coolant loops. The average leakage of water vapor from a pump mechanical seal was less than 1.4 lb/yr during a five-month period. The pump circulated deionized water at 260 deg C and 850 psig. (auth)

Research Organization:
Du Pont de Nemours (E.I.) & Co. Savannah River Lab., Aiken, S.C.
NSA Number:
NSA-15-029307
OSTI ID:
4842999
Report Number(s):
DP-611
Country of Publication:
United States
Language:
English

Similar Records

LEAKAGE OF WATER FROM GASKETED JOINTS PROPOSED FOR THE HWCTR. PART I
Technical Report · Fri Jul 01 00:00:00 EDT 1960 · OSTI ID:4129713

LEAKAGE OF WATER FROM VALVE STUFFING BOXES
Technical Report · Sat Dec 31 23:00:00 EST 1960 · OSTI ID:4088232

LEAKAGE OF WATER FROM PUMP MECHANICAL SEALS
Technical Report · Tue Oct 31 23:00:00 EST 1961 · OSTI ID:4816435