Examination of criticality accident alarm coverage on the operating floors of Buildings X-333, X-330, and X-326 at the Portsmouth Gaseous Diffusion Plant. Revision 1
The diffusion cascade processing equipment at the Portsmouth Gaseous Diffusion Plant (PORTS) is located in Buildings X-333, X-330, and X-326. These buildings were referred to as the cascade buildings. Because enriched uranium operations are performed within the cascade buildings, the potential for a criticality accident in these buildings exists. A Criticality Accident Alarm System (CAAS) is in place to alarm in the event of a criticality accident. The CAAS is required to be designed to immediately detect the minimum accident-of-concern. A minimum accident-of-concern in an area with nominal shielding delivers the equivalent of an absorbed dose rate in free air of 20 rads per minute at a distance of 2 meters from the reacting material [Am86]. This report summarizes the analysis that was performed to evaluate the CAAS response to selected minimum accidents-of-concern on the operating floor of the cascade buildings. Selection of potential accident locations was based, in part, on the maximum distance to the closest CAAS detector. The other factor in selecting potential accident locations for analysis was the amount of intervening shielding between the accident location and CAAS detector. If the CAAS was predicted to alarm under conditions of significant shielding, then the system presumably would alarm in response to all accidents greater than the minimum accident-of-concern, at closer distances, and with less shielding.
- Research Organization:
- Portsmouth Gaseous Diffusion Plant, OH (United States)
- Sponsoring Organization:
- USDOE Assistant Secretary for Nuclear Energy, Washington, DC (United States); USDOE National Nuclear Security Administration (NNSA), Nuclear Criticality Safety Program (NCSP)
- DOE Contract Number:
- AC05-84OT21400
- OSTI ID:
- 481508
- Report Number(s):
- POEF-SH--38-Rev.1; ON: DE97007560
- Country of Publication:
- United States
- Language:
- English
Similar Records
Examination of criticality accident alarm coverage on the operating floors of the X-333, X-330, and X-326 facilities at the Portsmouth Gaseous Diffusion Plant
Verification of criticality accident alarm system detector locations for the X-326 process cell floor
An examination of criticality accident alarm coverage of the X-710, X-760 Buildings and the north half of the X-7745-R storage pad at the Portsmouth Gaseous Diffusion Plant
Technical Report
·
Sun Dec 31 23:00:00 EST 1995
·
OSTI ID:188621
Verification of criticality accident alarm system detector locations for the X-326 process cell floor
Technical Report
·
Mon Jul 31 20:00:00 EDT 1995
·
OSTI ID:110805
An examination of criticality accident alarm coverage of the X-710, X-760 Buildings and the north half of the X-7745-R storage pad at the Portsmouth Gaseous Diffusion Plant
Technical Report
·
Sun Dec 31 19:00:00 EST 1995
·
OSTI ID:201802