Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Advanced low noise cooling fans

Technical Report ·
OSTI ID:48141
 [1];  [2]
  1. Ventilatoren Sirocco Howden, Hengelo (Netherlands)
  2. Howden Fan Co., Hyde Park, MA (United States)

The results from an intensive research program show that it is possible to reduce the sound power level of cooling fans by 15 dB(A) by altering blade cord width and swept leading and trailing edge lines. Combination with the reduction of the pressure drop can result in a step of 20 dB(A) and a reduction with 25 percent of the absorbed power. Testing was conducted in accordance with recognized international measuring standards and the results will be presented, including consequences for cooling tower and condenser design.

Research Organization:
Electric Power Research Inst., Palo Alto, CA (United States); Yankee Scientific, Inc., Medfield, MA (United States)
OSTI ID:
48141
Report Number(s):
EPRI-TR--104867; CONF-9408224--
Country of Publication:
United States
Language:
English

Similar Records

Noise-emission characteristics of circular mechanical, natural, and fan-assist natural-draft cooling towers with silencers
Conference · Fri Dec 31 23:00:00 EST 1976 · Proc. Am. Power Conf.; (United States) · OSTI ID:6661189

Sound of low-speed fans
Conference · Fri Dec 31 23:00:00 EST 1976 · OSTI ID:5149047

Noise reduction in fossil power plant draft fans