Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Control strategy and site selection of a shunt active filter for damping of harmonic propagation in power distribution systems

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.568259· OSTI ID:477219
 [1]
  1. Okayama Univ. (Japan). Dept. of Electrical Engineering
This paper deals with a shunt active filter which will be installed by an electric utility, putting much emphasis on the control strategy and the best point of installation of the shunt active filter on a feeder in a power distribution system. The objective of the shunt active filter is to damp harmonic propagation, which results from harmonic resonance between many capacitors for power factor improvement and line inductors in the feeder, rather than to minimize voltage distortion throughout the feeder. Harmonic mitigation is a welcome ``by-product`` of the shunt active filter, which comes from damping of harmonic propagation. This paper concludes that the shunt active filter based on detection of voltage at the point of installation is superior in stability to others, and that the best site selection is not the beginning terminal but the end terminal of the primary line in the feeder. Computer simulation is performed to verify the validity and effectiveness of the shunt active filter by means of an analog circuit simulator, which is characterized by installing it on a feeder of a radial distribution system in a residential area.
OSTI ID:
477219
Report Number(s):
CONF-960111--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 1 Vol. 12; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

A shunt active power filter applied to high voltage distribution lines
Journal Article · Tue Dec 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:477209

A new power line conditioner for harmonic compensation in power systems
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Transactions on Power Delivery · OSTI ID:136591

Shunt capacitor sizing for radial distribution feeders with distorted substation voltages
Journal Article · Sat Mar 31 23:00:00 EST 1990 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) · OSTI ID:6737552