High performance control of harmonic instability from HVDC link system
Conference
·
OSTI ID:438737
- Korea Electric Power Research Inst., Taejeon (Korea, Republic of)
This paper investigates the usefulness of novel control method for HVDC link system which suffers from severe condition of low order harmonic. This control scheme is used the feedforward control method which is directly controlled dc current at dc link system. The studies of this paper are aimed to improving the dynamic response of HVdc link system in disturbances such as faults. To achieve those objectives, digital time domain simulations are employed by the electro magnetic transient program for dc system (EMTDC). This method results in stable recovery from faults at both rectifier and inverter terminal busbars for a HVdc system that is inherently unstable. It has been found to be robust and control performance has been enhanced.
- OSTI ID:
- 438737
- Report Number(s):
- CONF-951136--; ISBN 0-7803-2981-3
- Country of Publication:
- United States
- Language:
- English
Similar Records
Controlling harmonic instability of HVDC links connected to weak ac systems
Application of GTO voltage source inverter in a hybrid HVDC link
Solution to the problem of low order harmonic resonance from HVDC converters
Journal Article
·
Mon Oct 01 00:00:00 EDT 1990
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA)
·
OSTI ID:6457762
Application of GTO voltage source inverter in a hybrid HVDC link
Journal Article
·
Fri Dec 31 23:00:00 EST 1993
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:7115234
Solution to the problem of low order harmonic resonance from HVDC converters
Journal Article
·
Wed Oct 31 23:00:00 EST 1990
· IEEE Transactions on Power Systems (Institute of Electrical and Electronics Engineers); (USA)
·
OSTI ID:6075299