Passive shunt harmonic filters for low and medium voltage: A cost comparison study
Journal Article
·
· IEEE Transactions on Power Systems
- Graz Univ. of Technology (Austria)
- Worcester Polytechnic Inst., MA (United States)
This paper presents the cost of 480V and 13.8kV passive shunt harmonic filters tuned at 300, 420, 660 and 780 Hz. The cost is presented in function of the kVA of the load served by the filters, the 60Hz reactive power produced by the filter and the total non-60Hz apparent power of the load. The main conclusion of this work is that for nonlinear loads in excess of 1 MVA it is more economical to use filter centers connected on the 13.8kV side.
- OSTI ID:
- 435372
- Report Number(s):
- CONF-960111--
- Journal Information:
- IEEE Transactions on Power Systems, Journal Name: IEEE Transactions on Power Systems Journal Issue: 4 Vol. 11; ISSN 0885-8950; ISSN ITPSEG
- Country of Publication:
- United States
- Language:
- English
Similar Records
A shunt active power filter applied to high voltage distribution lines
A new approach to harmonic compensation in power systems; A combined system of shunt passive and series active filters
Compensation characteristics of the combined system of shunt passive and series active filters
Journal Article
·
Tue Dec 31 23:00:00 EST 1996
· IEEE Transactions on Power Delivery
·
OSTI ID:477209
A new approach to harmonic compensation in power systems; A combined system of shunt passive and series active filters
Journal Article
·
Wed Oct 31 23:00:00 EST 1990
· IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:5586038
Compensation characteristics of the combined system of shunt passive and series active filters
Journal Article
·
· IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6799946