Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Improved EHV line switching surge control by application of MO-arrestors and controlled switching

Conference ·
OSTI ID:433831
; ;  [1]
  1. ABB High Voltage Technologies Ltd., Zuerich-Oerlikon (Switzerland)
Transmission line switching surges and its limitation by means of metal-oxide (MO) surge arresters and controlled switching are discussed. The benefits of these overvoltage control methods are analyzed based on extensive simulation studies of 550 kV transmission lines. The line length is taken as independent parameter and the degree of shunt-compensation is considered as well. The simulation studies show that MO arresters and controlled switching cope in most cases with the insulation coordination requirements of 550 kV networks, thus eliminating the need of closing resistors.
OSTI ID:
433831
Report Number(s):
CONF-951136--; ISBN 0-7803-2981-3
Country of Publication:
United States
Language:
English

Similar Records

Switching surges: Part IV - Control and reduction on AC transmission lines
Journal Article · Sun Aug 01 00:00:00 EDT 1982 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6063099

Switching surge characteristics of six-phase transmission lines
Journal Article · Wed Oct 31 23:00:00 EST 1984 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5920816

Impact of shunt capacitor banks on substation surge environment and surge arrester applications
Journal Article · Tue Oct 01 00:00:00 EDT 1996 · IEEE Transactions on Power Delivery · OSTI ID:422764