Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Frequency relaying based on instantaneous frequency measurement

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.544251· OSTI ID:422755
; ;  [1]
  1. Univ. of Bath (United Kingdom). School of Electronic and Electrical Engineering
A frequency relay capable of under/over frequency and rate of change of frequency measurements has been implemented on a digital signal processor using an instantaneous frequency measuring algorithm. Careful attention to the filtering aspects of the relay is needed under dynamic conditions due to frequency modulation of the input signal. An algorithm for avoiding unwanted relay operation due to impulsive changes in the input signal is presented. Results are shown for simulated tests using computer based relay testing equipment, and for overloads on a micromachine power system simulator.
OSTI ID:
422755
Report Number(s):
CONF-960111--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 4 Vol. 11; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Model system tests on a new numeric method of power system frequency measurement
Journal Article · Sun Mar 31 23:00:00 EST 1996 · IEEE Transactions on Power Delivery · OSTI ID:244803

Transients computation for relay testing in real-time
Journal Article · Fri Jul 01 00:00:00 EDT 1994 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6963078

EMTP transient modeling of a distance relay and a comparison with EMTP laboratory testing. [ElectroMagnetics Transient Program]
Journal Article · Thu Jul 01 00:00:00 EDT 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:6093970