  2. Rockefeller Associates, Inc., Morris Plains, NJ (United States)
Differential relays are used extensively to provide protection for power transformers. Several issues must be considered in their application to ensure adequate protection. These include transformer magnetizing inrush current, relay burden and current transformer performance. The use of low ratio current transformers in high magnitude fault applications can produce distorted secondary waveforms to the relay whose performance may be directly affected. There is also a relationship between the magnetizing inrush and current transformer performance which may affect the operation of the differential relay. This paper discusses these specific applications and the testing of a transformer differential relay under conditions of saturated CT`s using the Electro-Magnetic Transient Program (EMTP).
OSTI ID:
415505
Report Number(s):
CONF-9510203--
Country of Publication:
United States
Language:
English

Similar Records

Experimental evaluation of EMTP-based current transformer models for protective relay transient study. [Electro Magnetic Transient Program]
Journal Article · Fri Dec 31 23:00:00 EST 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7236999

A Kalman filter based digital percentage differential and ground fault relay for a 3-phase power transformer
Journal Article · Sun Jul 01 00:00:00 EDT 1990 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (USA) · OSTI ID:6801440

A new technique of differential relaying: the A-differential relay
Journal Article · Fri Oct 01 00:00:00 EDT 1982 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:5958454