DEVELOPMENT OF TEMPERATURE PROTECTIVE CIRCUITS FOR THE HNPF FUEL CHANNEL EXIT
Technical Report
·
OSTI ID:4153326
The HNPF plant protective system includes circuits with the function of precluding unsafe high temperature and sustained fast changes in fuel-charuel coolant-exit temperatures, either in the increasing or decreasing direction. The development of the fuel-charuel exit high temperature and rate change of temperature circuits resulted in a transistorized system of plug-in components of high reliability. The circuits were designed, where possible, for fail-safe operation in case of component malfunction; and for ease of maintenance and calibrationIn addition to providing shutdown or scram signals, these circuits also provide setback and alarm signals. The setpoints for scram, setback, and alarm are each independently adjustable. These circuits monitor an iron- constantan thermocouple located at the outlet of a fuel cluster in the reactor. In the actual protective system, three identical Circuits are used in a 2-out-of- 3 coincidence arrangement to enhance the over-all reliability. (auth)
- Research Organization:
- Atomics International. Div. of North American Aviation, Inc., Canoga Park, Calif.
- DOE Contract Number:
- AT(11-1)-GEN-8
- NSA Number:
- NSA-14-018629
- OSTI ID:
- 4153326
- Report Number(s):
- NAA-SR-5313
- Country of Publication:
- United States
- Language:
- English
Similar Records
DEVELOPMENT OF TEMPERATURE PROTECTIVE CIRCUITS FOR THE HNPF FUEL CHANNEL EXIT
ANALOG STUDY OF THE HNPF PROTECTIVE SYSTEM FOR THE U-Mo CORE
Use of digital computers in the protection system for Savannah River reactors
Technical Report
·
Sat Jan 14 23:00:00 EST 1961
·
OSTI ID:4088142
ANALOG STUDY OF THE HNPF PROTECTIVE SYSTEM FOR THE U-Mo CORE
Technical Report
·
Thu Jul 16 00:00:00 EDT 1959
·
OSTI ID:4807079
Use of digital computers in the protection system for Savannah River reactors
Conference
·
Wed Jun 01 00:00:00 EDT 1977
·
OSTI ID:7095531