Application considerations and compensation characteristics of shunt active and series active filters in power systems
- Tennessee Univ., Knoxville, TN (United States)
- Oak Ridge National Lab., TN (United States)
This paper characterizes typical nonlinear loads into two types of harmonic sources -harmonic current source and harmonic voltage source, which produce highly distorted currents and voltages, respectively. The conventional approach of active harmonic compensation has been the parallel type or `shunt active filter.` It is shown in this paper that the shunt active filter is effective only to harmonic current sources but not to harmonic voltage sources. On the other hand, the active filter connected in series with the system or `series active filter` is very effective in suppression of the harmonic voltage sources. General compensation characteristics of shunt active filters and series active filters are given analytically. The features, required operation conditions, and application considerations of both filters are described analytically and demonstrated experimentally.