Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Calculation of interturn voltages in machine windings during switching transients measured on terminals

Journal Article · · IEEE Transactions on Energy Conversion
DOI:https://doi.org/10.1109/60.372572· OSTI ID:40287
 [1];  [2];  [3]
  1. ITM, Morelia (Mexico)
  2. IIE, Cuernavaca (Mexico)
  3. UMIST, Manchester (United Kingdom)
This paper describes a technique for calculating interturn voltages in machine windings during transient conditions. The technique is based on the measurement of switching transients at the machine terminals and computer simulation of the surge travelling through the winding. The machine winding is treated as a multiconductor transmission line and the Discrete Fourier Transform and convolution techniques are used for calculating the switching transient distribution along the winding. Switching transients results obtained on two electrical motors in the Manzanillo 2 power plant are used in the analysis.
OSTI ID:
40287
Report Number(s):
CONF-940702--
Journal Information:
IEEE Transactions on Energy Conversion, Journal Name: IEEE Transactions on Energy Conversion Journal Issue: 1 Vol. 10; ISSN 0885-8969; ISSN ITCNE4
Country of Publication:
United States
Language:
English

Similar Records

A three-phase model for surge distribution studies in electrical machines
Journal Article · Fri Feb 28 23:00:00 EST 1997 · IEEE Transactions on Energy Conversion · OSTI ID:465115

Transients during 138-kV SF6 breaker switching of low inductive currents
Journal Article · · IEEE Transactions on Industry Applications (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:5798169

Overvoltages in a finite-length underground cable by multiple reflections of transient voltages
Conference · · Journal of the Tennessee Academy of Science; (United States) · OSTI ID:7188792