Tests show ability of vacuum circuit breaker to interrupt fast transient recovery voltage rates of rise of transformer secondary faults

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.368390· OSTI ID:39983
 [1]
  1. Westinghouse Science and Technology Center, Pittsburgh, PA (United States)

A vacuum circuit breaker demonstrated its ability to interrupt short circuits with faster than normal rates of rise of transient recovery voltage (TRV) at levels greater than those produced by most transformer secondary faults. Two recent exploratory test programs evaluated the interrupting ability of a 15kV vacuum circuit breaker containing interrupters of the rotating arc type with contacts made from a chromium-copper powder metal mixture. The interrupting conditions covered a wide range of currents from 10% to 130% of the 28kA rated short circuit current of the tested circuit breaker and a wide range of TRV rates of rise, including the relatively slow rate of rise, normally used in testing and found in most indoor circuit breaker applications, two faster rates of rise equaling and exceeding those found in a known power plant transformer secondary protection application, and the fastest rates of rise possible in the laboratory which exceed the requirements of most transformer secondary faults. These tests showed that the interrupting performance of the tested vacuum circuit breaker was unaffected by the TRV rate of rise to the fastest rates available in the test lab. Such a vacuum circuit breaker can therefore be used without TRV modifying capacitors to slow down the rate of rise provided by the power system. This ability is particularly important if analysis shows that the expected TRV from a transformer secondary fault has a fast rate of rise beyond the recognized ability of an older circuit breaker to acceptably interrupt.

OSTI ID:
39983
Report Number(s):
CONF-9404175--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 1 Vol. 10; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

Tests show ability of vacuum circuit breaker to interrupt fast transient recovery voltage rates of rise of transformer secondary faults
Conference · Fri Dec 30 23:00:00 EST 1994 · OSTI ID:152703

Proposed transient recovery voltage ratings for power circuit breakers
Journal Article · Thu Jul 01 00:00:00 EDT 1965 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6922325

Direct current momentary circuit interrupter
Patent · Tue Jun 06 00:00:00 EDT 2023 · OSTI ID:1998458