Use of inverse time, adjustable instantaneous pickup circuit breakers for short circuit and ground fault protection of energy efficient motors

Conference ·
OSTI ID:392601
 [1];  [2]
  1. General Electric Co., Plainville, CT (United States)
  2. Bechtel Corp., Houston, TX (United States)
Many energy efficient low voltage motors exhibit first half cycle instantaneous inrush current values greater than the National Electrical Code`s 13 times motor full load amperes maximum permissible setting for instantaneous trip circuit breakers. The alternate use of an inverse time circuit breaker could lead to inadequate protection if the breaker does not have adjustable instantaneous settings. Recent innovations in digital solid state trip unit technology have made available an inverse time, adjustable instantaneous trip circuit breaker in 15A to 150A ratings. This allows the instantaneous pickup to be adjusted to a value slightly above motor inrush so that low level faults will be cleared instantaneously while avoiding nuisance tripping at startup. Applications, settings and comparisons are discussed.
OSTI ID:
392601
Report Number(s):
CONF-950920--; ISBN 0-7803-2909-0
Country of Publication:
United States
Language:
English

Similar Records

Test of circuit breakers under harmonic loading conditions. Final report
Technical Report · Tue Oct 31 23:00:00 EST 1995 · OSTI ID:250575

Field tests of a circuit breaker synchronous control
Journal Article · Sat Jul 01 00:00:00 EDT 1995 · IEEE Transactions on Power Delivery · OSTI ID:136562

Circuit breaker operation and potential failure modes during an earthquake
Conference · Wed Dec 31 23:00:00 EST 1986 · OSTI ID:5855565