Performance of gas-insulated substations and associated grounding networks during fault and transient conditions

Conference ·
OSTI ID:389985
 [1]; ; ;  [2]
  1. Korea Industrial Safety Corp., Inchon (Korea, Republic of)
  2. Safe Engineering Services and Technologies Ltd., Montreal, Quebec (Canada)
This paper discusses in detail the electric modeling of the overhead tubular enclosures of a 500 kV circuit breaker in a gas insulated substation. Under both steady-state and phase-to-ground fault conditions, the current distribution on the enclosure as well as the spatial distribution of the scalar potentials and electromagnetic fields near the circuit breaker are computed at different frequencies for various wire-mesh models of the breaker enclosure. The selected frequencies are representative of those present in the frequency spectrum of typical lightning transient currents. The different models of the breaker enclosure are obtained by varying the number of conductors used to represent the enclosure. For a given enclosure diameter and length, the minimum number of conductors required to obtain satisfactory current distribution and electromagnetic field results at different frequencies are determined.
OSTI ID:
389985
Report Number(s):
CONF-960426--
Country of Publication:
United States
Language:
English

Similar Records

Transient performance of substation structures and associated grounding systems
Journal Article · Mon May 01 00:00:00 EDT 1995 · IEEE Transactions on Industry Applications · OSTI ID:55484

Electromagnetic transients in substations. Volume 3, Test results: Final report
Technical Report · Wed Mar 31 23:00:00 EST 1993 · OSTI ID:10172333

Electromagnetic transients in substations. Volume 2, Models, validations, and simulations: Final report
Technical Report · Wed Mar 31 23:00:00 EST 1993 · OSTI ID:10172336