A new time domain voltage source model for an arc furnace using EMTP
Journal Article
·
· IEEE Transactions on Power Delivery
- Clemson Univ., SC (United States). Dept. of Electrical and Computer Engineering
This paper presents a new time domain Controlled Voltage Source (CVS) model for an arc furnace using the Electro Magnetic Transients Program (EMTP). The developed model is based on a piece wise linear approximation of the v-i characteristic of the arc furnace load. In addition to this, the novelty of this simulation technique lies in the fact that the active power consumed by the load is also considered in the proposed load model, thus making the proposed load model dependent on the operating conditions of the load. Dynamic variation of the arc is incorporated through sinusoidal and band limited white noise variation of the arc resistance in the v-i characteristic of the arc furnace load. Depending on the variation of the arc resistance, the developed load model accurately represents both static (deterministic) and dynamic (random) arc characteristics. While static arc models are useful for harmonic studies, dynamic models are useful for power quality studies and in particular, the study of voltage flicker. The results are compared with actual voltage measurements taken from a local utility to prove the validity of the proposed load model.
- OSTI ID:
- 372263
- Report Number(s):
- CONF-960111--
- Journal Information:
- IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 3 Vol. 11; ISSN 0885-8977; ISSN ITPDE5
- Country of Publication:
- United States
- Language:
- English
Similar Records
Arc-furnace model for the study of flicker compensation in electrical networks
Voltage flicker prediction for two simultaneously operated ac arc furnaces
Arc furnace flicker measurements and control
Journal Article
·
Sat Oct 01 00:00:00 EDT 1994
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6808655
Voltage flicker prediction for two simultaneously operated ac arc furnaces
Journal Article
·
Mon Mar 31 23:00:00 EST 1997
· IEEE Transactions on Power Delivery
·
OSTI ID:492215
Arc furnace flicker measurements and control
Journal Article
·
Thu Dec 31 23:00:00 EST 1992
· IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States)
·
OSTI ID:6356565