Fault component reactance relay

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.517483· OSTI ID:372217
; ;  [1]
  1. Nanjing Automation Research Inst. (China)
A new distance relay is developed in this paper. The relay is based on two operation criteria--a current criterion and a voltage criterion. Each uses the fault component as operating quantity, and the relay reacts only on the reactance of the transmission line. So, it is a fault component reactance relay. During external fault, two criteria are complementary to each other, i.e., at least one of them will not be satisfied. So no maloperation will happen. During internal fault both criteria will be satisfied even if the fault resistance is high.
OSTI ID:
372217
Report Number(s):
CONF-960111--
Journal Information:
IEEE Transactions on Power Delivery, Journal Name: IEEE Transactions on Power Delivery Journal Issue: 3 Vol. 11; ISSN 0885-8977; ISSN ITPDE5
Country of Publication:
United States
Language:
English

Similar Records

An accurate fault locator with compensation for apparent reactance in the fault resistance resulting from remote-end infeed
Journal Article · Thu Jan 31 23:00:00 EST 1985 · IEEE Trans. Power Appar. Syst.; (United States) · OSTI ID:6120362

Application of block pulse functions in a polyphase digital distance relay
Conference · Sat Dec 30 23:00:00 EST 1995 · OSTI ID:415570

Adaptive relay setting for stand-alone digital distance protection
Journal Article · Fri Dec 31 23:00:00 EST 1993 · IEEE Transactions on Power Delivery (Institute of Electrical and Electronics Engineers); (United States) · OSTI ID:7304317