skip to main content
OSTI.GOV title logo U.S. Department of Energy
Office of Scientific and Technical Information

Title: Accurate modelling of rod driven tower footing

Journal Article · · IEEE Transactions on Power Delivery
DOI:https://doi.org/10.1109/61.517523· OSTI ID:372145
;  [1]
  1. IST-Univ. Tecnica de Lisboa/Instituto da Energia-INTERG (Portugal)

For evaluating the lightning performance of transmission lines by computer simulation, the accurate modelling of tower footing is very important. In particular, the decrease of the earth resistance observed for high values of the current flowing from the tower to earth has to be considered. In this paper, different modelling approaches allowing to take into account the non-linear behavior of the tower footing are overviewed, and a new model to describe the soil ionization process is presented. The proposed model corresponds to considering the ionized soil region as an equifield shell. In order to represent the ionization phenomena, the values of the resistivity on the ionized region are decreased according to the local current density, and the electric field is kept at a critical value. Deionization of the soil is also taken into account. Simulation results are presented, and compared to the published results of experimental tests.

OSTI ID:
372145
Journal Information:
IEEE Transactions on Power Delivery, Vol. 11, Issue 3; Other Information: DN: Presented at the 1995 ESMO conference, October 29--November 3, 1995, Columbus, OH (US); PBD: Jul 1996
Country of Publication:
United States
Language:
English