Engineering work plan and design basis for 241-SY ventilation improvements
There are three tanks in the 241-SY tank farm. Tank 241-SY101 and 241-SY-103 are flammable gas watch list tanks. Tank 241-SY-102 is included in the ventilation improvement process in an effort to further control air flow in the tank farm. This tank farm has only one outlet ventilation port for all three tanks. Flammable gas is released (may be steady and/or periodic) from the waste in the primary tank vapor space. The gas is removed from the tank by an active ventilation system. However, maintaining consistent measurable flow through the tank can be problematic due to the poor control capabilities of existing equipment. Low flow through the tank could allow flammable gas to build up in the tank and possibly exceed the lower flammability limit (LFL), prevent the most rapid removal of flammable gas from the tank after a sudden gas release, and/or cause high vacuum alarms to sound. Using the inlet and outlet down stream butterfly valves performs the current method of controlling flow in tank farm 241-SY. A filter station is installed on the inlet of each tank, but controlling air flow with its 12 inch butterfly valve is difficult. There is also in-leakage through pump and valve pits. Butterfly valves on the downstream side of each tank could also be used to control air flow. However, their large size and the relatively low air velocity make this control method also ineffective. The proposed method of optimizing tank air flow and pressure control capability is to install an air flow controller on the inlet of each existing filter station in SY farm, and seal as best as practical all other air leakage paths. Such air flow controllers have been installed on 241-AN and 241-AW tanks (see drawing H-2-85647).
- Research Organization:
- Fluor Daniel Hanford Inc., Richland, WA (United States)
- Sponsoring Organization:
- USDOE Office of Environmental Restoration and Waste Management, Washington, DC (United States)
- DOE Contract Number:
- AC06-96RL13200
- OSTI ID:
- 362459
- Report Number(s):
- HNF-SD-WM-WP--343; ON: DE99051019; BR: EW3120074
- Country of Publication:
- United States
- Language:
- English
Similar Records
Operational test report for 241-AW tank inlet air control stations
Double shell tank primary ventilation exhaust flow monitor system design description
Technical basis for installation of the double shell tank exhaust flow monitoring systems
Technical Report
·
Wed Jul 03 00:00:00 EDT 1996
·
OSTI ID:659220
Double shell tank primary ventilation exhaust flow monitor system design description
Technical Report
·
Mon Mar 10 23:00:00 EST 1997
·
OSTI ID:325637
Technical basis for installation of the double shell tank exhaust flow monitoring systems
Technical Report
·
Mon Mar 10 23:00:00 EST 1997
·
OSTI ID:325636