Title: Condensation of downward-flowing zeotropic mixture HCFC-123/HFC-134a on a staggered bundle of horizontal low-finned tubes

Journal Article · · Journal of Heat Transfer
DOI:https://doi.org/10.1115/1.2825993· OSTI ID:361756
; ;  [1]
  1. Kyushu Univ., Kasuga, Fukuoka (Japan). Inst. of Advanced Material Study

Experiments were conducted to obtain row-by-row heat transfer data during condensation of downward-flowing zeotropic refrigerant mixture HCFC-123/HFC-134a on a 3 x 15 (columns x rows) staggered bundle of horizontal low-finned tubes. The vapor temperature and the HFC-134a mass fraction at the tube bundle inlet were maintained at about 50 C and 9%, respectively. The refrigerant mass velocity ranged from 9 to 34 kg/m{sup 2} s, and the condensation temperature difference from 3 to 12 K. The measured distribution of the vapor mass fraction in the tube bundle agreed fairly well with that of the equilibrium vapor mass fraction. The vapor phase mass transfer coefficient was obtained from the heat transfer data by subtracting the thermal resistance of the condensate film. The heat transfer coefficient and the mass transfer coefficient decreased significantly with decreasing mass velocity. These values first increased with the row number up to the third (or second) row, then decreased monotonically with further increasing row number, and then increased again at the last row. The mass transfer coefficient increased with condensation temperature difference, which was due to the effect of suction associated with condensation. On the basis of the analogy between heat and mass transfer, a dimensionless correlation of the mass transfer coefficient for the 4th to 14th rows was developed.

Sponsoring Organization:
USDOE
OSTI ID:
361756
Journal Information:
Journal of Heat Transfer, Vol. 121, Issue 2; Other Information: PBD: May 1999
Country of Publication:
United States
Language:
English