Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Condensation of downward-flowing zeotropic mixture HCFC-123/HFC-134a on a staggered bundle of horizontal low-finned tubes

Journal Article · · Journal of Heat Transfer
DOI:https://doi.org/10.1115/1.2825993· OSTI ID:361756
; ;  [1]
  1. Kyushu Univ., Kasuga, Fukuoka (Japan). Inst. of Advanced Material Study

Experiments were conducted to obtain row-by-row heat transfer data during condensation of downward-flowing zeotropic refrigerant mixture HCFC-123/HFC-134a on a 3 x 15 (columns x rows) staggered bundle of horizontal low-finned tubes. The vapor temperature and the HFC-134a mass fraction at the tube bundle inlet were maintained at about 50 C and 9%, respectively. The refrigerant mass velocity ranged from 9 to 34 kg/m{sup 2} s, and the condensation temperature difference from 3 to 12 K. The measured distribution of the vapor mass fraction in the tube bundle agreed fairly well with that of the equilibrium vapor mass fraction. The vapor phase mass transfer coefficient was obtained from the heat transfer data by subtracting the thermal resistance of the condensate film. The heat transfer coefficient and the mass transfer coefficient decreased significantly with decreasing mass velocity. These values first increased with the row number up to the third (or second) row, then decreased monotonically with further increasing row number, and then increased again at the last row. The mass transfer coefficient increased with condensation temperature difference, which was due to the effect of suction associated with condensation. On the basis of the analogy between heat and mass transfer, a dimensionless correlation of the mass transfer coefficient for the 4th to 14th rows was developed.

Sponsoring Organization:
USDOE
OSTI ID:
361756
Journal Information:
Journal of Heat Transfer, Journal Name: Journal of Heat Transfer Journal Issue: 2 Vol. 121; ISSN 0022-1481; ISSN JHTRAO
Country of Publication:
United States
Language:
English

Similar Records

Potentially acceptable substitutes for the chlorofluorocarbons: Properties and performance features of HFC-134a, HCFC-123, and HCFC-141b
Conference · Mon May 01 00:00:00 EDT 1989 · International Journal of Thermophysics; (USA) · OSTI ID:5568606

Thermal conductivity of halogenated ethanes, HFC-134a, HCFC-123, and HCFC-141b
Journal Article · Thu Dec 31 23:00:00 EST 1992 · International Journal of Thermophysics; (United States) · OSTI ID:7071549

Performance evaluation of two azeotropic refrigerant mixtures of HFC-134a with R-290 (propane) and R-600a (isobutane)
Journal Article · Wed Jun 01 00:00:00 EDT 1994 · Journal of Energy Resources Technology; (United States) · OSTI ID:7249819