A practical application for the chemical treatment of Southern California`s reclaimed, Title 22 water for use as makeup water for recirculating cooling water systems

Conference ·
OSTI ID:352584
 [1]; ;  [2]
  1. Calgon Corp., Pittsburgh, PA (United States)
  2. County Sanitation Districts of Los Angeles County, Whittier, CA (United States)

Pilot cooling water studies conducted at a Southern California landfill/cogeneration station demonstrated a successful chemical treatment program for recirculating cooling water that used unnitrified, reclaimed, Title 22 water as the primary makeup water source. The constituents in the reclaimed water are supplied by variety of residential and waste water sources resulting in a water quality that may vary to a greater degree than domestic water supplies. This water contains high concentrations of orthophosphate, ammonia, chlorides and suspended solids. The impact of which, under cycled conditions is calcium orthophosphate scaling, high corrosion of yellow metal and mild steel, stress cracking of copper alloys and stainless steel and rapidly growing biological activity. A mobile cooling water testing laboratory with two pilot recirculating water systems modeled the cogeneration station`s cooling tower operating conditions and parameters. The tube and shell, tube side cooling heat exchangers were fitted with 443 admiralty, 90/10 copper nickel, 316 stainless steel and 1202 mild steel heat exchanger tubes. Coupons and Corrater electrodes were also installed. A chemical treatment program consisting of 60/40 AA/AMPS copolymer for scale, deposits and dispersion, sodium tolyltriazole for yellow metal corrosion, and a bromination program to control the biological activity was utilized in the pilot systems. Recirculating water orthophosphate concentrations reached levels of 70 mg/L as PO, and ammonia concentrations reached levels of 35 mg/L, as total NH3. The study successfully demonstrated a chemical treatment program to control scale and deposition, minimize admiralty, 90/10 copper nickel and carbon steel corrosion rates, prevent non-heat transfer yellow metal and stainless steel stress cracking, and control the biological activity in this high nutrient water.

OSTI ID:
352584
Report Number(s):
CONF-980316--
Country of Publication:
United States
Language:
English

Similar Records

Water treatment cuts deposition at oil and solvent recovery plant
Journal Article · Tue Oct 01 00:00:00 EDT 1985 · Chem. Process. (Chicago); (United States) · OSTI ID:5509555

A better cooling water system
Journal Article · Mon Nov 30 23:00:00 EST 1987 · Hydrocarbon Process.; (United States) · OSTI ID:5394005

A new cooling water treatment program balances refinery and petrochemical plant needs
Conference · Mon Dec 31 23:00:00 EST 1979 · Natl. Refiners Assoc. Annu. Meet. Pap.; (United States) · OSTI ID:6367377