Cooling tower fill fouling control in a geothermal power plant

Conference ·
OSTI ID:351764
; ;  [1];  [2]
  1. Nalco Chemical Co., Naperville, IL (United States)
  2. CalEnergy Operating Co., Calipatria, CA (United States)

Since its first introduction to the market in the 1970s, cooling tower film fill technology has significantly increased thermal performance and reduced the size of cooling towers. However, the narrow spaces between film fill sheets make them susceptible to fouling. Without proper chemical treatment, deposits can accumulate within the film fill resulting in reduced tower efficiency, increased fouling and plugging of the fill. These phenomena could eventually lead to collapse of the tower structure, This paper describes a new approach to remedy the high efficiency film fill fouling problem in a geothermal power plant. The plant has a long history of fill fouling problems due to a very complex make-up water chemistry and desert-related environmental conditions. In recent years, various biocide and biodispersant treatments have significantly improved fouling control by slowing down tower fill deposition rates. However, no program has been successful in reducing fill weights, especially during the summer months. Within six weeks after starting a new control program, the average weight of the tower fill deposits dropped 22% and thermal performance of the cooling tower increased 20%. The treatment resulted in significant improvements in cooling tower operation and power production efficiency.

OSTI ID:
351764
Report Number(s):
CONF-980316--
Country of Publication:
United States
Language:
English

Similar Records

Pilot scale cooling tower fouled fill treatment: AFCATT (Anti-Fouling Chemical Additive Test Tower)
Technical Report · Tue Jan 31 23:00:00 EST 1995 · OSTI ID:48142

Fouling of cooling tower film fill: Causes, cleanup techniques and operating guidelines
Technical Report · Tue Jan 31 23:00:00 EST 1995 · OSTI ID:48144

AFCATT (Anti-Fouling Chemical Additive Test Tower)
Technical Report · Thu Jun 01 00:00:00 EDT 1995 · OSTI ID:121538