Skip to main content
U.S. Department of Energy
Office of Scientific and Technical Information

Study of how sash movement affects performance of fume hoods

Conference ·
OSTI ID:350001
 [1]
  1. TSI Incorporated, St. Paul, MN (United States)

This study was conducted to determine how sash movements affect the performance of fume hoods. The performance of two fume hoods was studied as the sashes were moved from closed to open position at speeds of 2 ft/s, 1.5 ft/s, and 1 ft/s. The tests were conducted with fume hoods operated at both constant volume and variable air volume. The tests indicate that sash movements can disturb airflow patterns at the face of the hood and potentially affect the performance of the hood. The effect of the sash movement varied with hood type and speed of sash movement. The faster sash movements of 2 ft/s and 1.5 ft/s had a greater effect on the performance of the hoods than the slower movement of 1 ft/s. Constant-volume hoods and variable-air-volume hoods were both affected by sash movements. Constant-volume hoods set to a full open face velocity of 60 ft/min were more susceptible to the sash movement than at 100 ft/min full open face velocity. The performance of variable-air-volume hoods is affected not only by sash movement speed but also by the response time of the controller. The drop in face velocity that occurs when the sash is moved is determined by the speed of the VAV controller. The required response time for containment depends on the fume hood design and the speed of the sash movement.

OSTI ID:
350001
Report Number(s):
CONF-970668--
Country of Publication:
United States
Language:
English

Similar Records

Fume hood performance: Using a bypass in variable air volume systems
Journal Article · Thu Oct 01 00:00:00 EDT 1998 · Applied Occupational and Environmental Hygiene · OSTI ID:290243

Fume hood performance: Face velocity variability inconsistent air volume systems
Journal Article · Tue Sep 01 00:00:00 EDT 1998 · Applied Occupational and Environmental Hygiene · OSTI ID:290247

Mock-up and testing of a variable volume laboratory fume hood exhaust system
Technical Report · Mon Dec 31 23:00:00 EST 1979 · OSTI ID:5709671