Measurements of the Effects of Smoke on Active Circuits
Journal Article
·
· Fire and Materials
- Sandia National Laboratories
Smoke has long been recognized as the most common source of fire damage to electrical equipment; however, most failures have been analyzed after the fire was out and the smoke vented. The effects caused while the smoke is still in the air have not been explored. Such effects have implications for new digital equipment being installed in nuclear reactors. The U.S. Nuclear Regulatory Commission is sponsoring work to determine the impact of smoke on digital instrumentation and control. As part of this program, Sandia National Laboratories has tested simple active circuits to determine how smoke affects them. These tests included the study of three possible failure modes on a functional board: (1) circuit bridging, (2) corrosion (metal loss), and (3) induction of stray capacitance. The performance of nine different circuits was measured continuously on bare and conformably coated boards during smoke exposures lasting 1 hour each and continued for 24 hours after the exposure started. The circuit that was most affected by smoke (100% change in measured values) was the one most sensitive to circuit bridging. Its high impedance (50 M{Omega}) was shorted during the exposure, but in some cases recovered after the smoke was vented. The other two failure modes, corrosion and induced stray capacitance, caused little change in the function of the circuits. The smoke permanently increased resistance of the circuit tested for corrosion, implying that the cent acts were corroded. However, the change was very small (< 2%). The stray-capacitance test circuit showed very little change after a smoke exposure in either the short or long term. The results of the tests suggest that conformal coatings and type of circuit are major considerations when designing digital circuitry to be used in critical control systems.
- Research Organization:
- Sandia National Labs., Albuquerque, NM (US); Sandia National Labs., Livermore, CA (US)
- Sponsoring Organization:
- US Department of Energy (US)
- DOE Contract Number:
- AC04-94AL85000
- OSTI ID:
- 3500
- Report Number(s):
- SAND97-2029J
- Journal Information:
- Fire and Materials, Journal Name: Fire and Materials
- Country of Publication:
- United States
- Language:
- English
Similar Records
Measurements of the effects of smoke on active circuits
Effects of smoke on functional circuits
Circuit bridging of components by smoke
Technical Report
·
Wed Dec 31 23:00:00 EST 1997
·
OSTI ID:634071
Effects of smoke on functional circuits
Technical Report
·
Wed Oct 01 00:00:00 EDT 1997
·
OSTI ID:552763
Circuit bridging of components by smoke
Technical Report
·
Tue Oct 01 00:00:00 EDT 1996
·
OSTI ID:414378